P9 ASD Installation and Operation Manual
Jump Frequency 1 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 1
).
Direct Access Number — F271
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency 2
Program
Special
Jump Frequencies
This parameter is the same as
Jump Frequency 1
) and is used when
multiple frequencies are to be jumped (see the plus-or-minus value setting at
). When multiple jump frequencies overlap, the system will recognize the
lowest and the highest frequencies as one jump range.
Direct Access Number — F272
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Jump Frequency 2 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 2
).
Direct Access Number — F273
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program
Special
Jump Frequencies
This parameter is the same as
Jump Frequency 1
) and is used when
multiple frequencies are to be jumped (see the plus-or-minus value setting at
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Jump Frequency 3 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency 3
).
Direct Access Number — F275
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Preset Speed 8
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as
Preset Speed 8
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
.
See
for additional information on this parameter.
Direct Access Number — F287
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — Lower-Limit Freq. (
)
Maximum — Upper-Limit Freq. (
Units — Hz
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......