246
P9 ASD Installation and Operation Manual
32
33
Torque Limit Switching 1/Torque Limit Switching 2
— Activating combinations of discrete input terminals
Torque Limit Switching 1
and
2
allow for the selection of a torque limit switching
profile as listed below.
34
35
36
37
PID Off
— Turns off
PID
control.
38
39
Pattern Operation Group 1
— Initiates the
Pattern 1 Pattern Run
.
40
41
Pattern Operation Group 2
— Initiates the
Pattern 2 Pattern Run
.
42
43
Pattern Operation Continuation
— Initiates a continuation of the last
Pattern Run
from its stopping point.
44
45
Pattern Operation Trigger
— Initiates the first
Preset Speed
of a
Pattern Run
and initiates each subsequent
enabled
Preset Speed
with continued activations.
46
47
External Over-Heat
— Causes an
Over-Heat Trip
(OH).
48
49
Hand Priority
(cancels serial priority) — Overrides any serial control and returns the
Command
and
Frequency
control to the settings of
50
51
Hold
(3-Wire Stop) — Decelerates the motor to a stop.
52
53
PID Differentiation/Integration Clear
— Clears the PID value.
54
55
PID Forward/Reverse Switching
— Toggles the gradient characteristic of the feedback response of the
V/I
terminal during PID-controlled operation.
56
57
Forced Continuous Operation
— Ignore PID control settings for the duration of activation.
58
59
Specified Speed
Operation
— Runs speed as commanded by the
Frequency Mode
setting.
60
61
Dwell Signal
— Used in conjunction with the
Acceleration/Deceleration Suspend
function (
) — suspends the
Accel/Decel function for the duration of the activation.
62
63
Power Failure Synchronized Signal
—
Activates the
Synchronized Accel/Decel
function of the
Regenerative
Power Ridethrough
feature. See
for additional information on this terminal setting.
64
65
My Function Run
— Activates the configured
My Function
feature. See
for additional information on this
parameter.
66
67
Autotuning Signal
— Initiates the
Autotune
function. Set
to
Autotuning by Input Terminal Signal
.
68
69
Speed Gain Switching
— Toggles the ASD operating mode from and to
Speed Control
and
Torque Control
.
Speed Control
operation references settings
and
.
Torque Control
operation references settings
and
70
71
Servo Lock
— Holds the motor at 0 Hz until a
Run
command is received.
72
73
Simple Positioning
— While operating in the
Positioning Control
mode, activation initiates the
Stop
command.
See
for additional information on this terminal setting.
74
75
kWH Display Clear
— Clears the kWH meter display.
76
77
Trace Back Trigger
— Initiates the data Read/Store function of the
Trace Selection
parameter. See
for
additional information on this feature.
78
79
Light-Load High-Speed Disable
— Terminates the Light-Load High-Speed operation.
NO/NC = Normally Open/Normally Closed.
*Selection numbers are used when configuring the ASD via communications. The Normally Open (NO) or Normally
Closed (NC) configuration must be chosen by selecting the associated number.
Table 6. Discrete Input Terminal Assignment Selections and Descriptions. (Continued)
*Sel. No.
Terminal Selection Descriptions
NO NC
Torque Limit
Switching Terminal
Torque Limit Selection
#1
#2
0
0
1
0
1
2
1
0
3
1
1
4
1=Terminal Activated
The 1 – 4 settings of the torque limit switching
selections are performed at
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......