P9 ASD Installation and Operation Manual
Second Speed Loop Proportional Gain
Program
Feedback
PG Settings
During closed-loop operation, this parameter sets the sensitivity of the ASD
when monitoring the output speed for control.
The larger the value entered here, the more sensitive the ASD is to changes in
the received feedback.
Direct Access Number — F463
Parameter Type —
Numerical
Factory Default —
12
Changeable During Run —
No
Minimum — 1
Maximum — 9999
Second Speed Loop Stabilization Coefficient
Program
Feedback
PG Settings
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the quicker the response to changes in the
received feedback.
Direct Access Number — F464
Parameter Type —
Numerical
Factory Default —
1
Changeable During Run —
Yes
Minimum — 1
Maximum — 9999
Load Moment of Inertia 2
Program
Feedback
PG Settings
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the
Drooping Control
mode.
Direct Access Number — F465
Parameter Type —
Numerical
Factory Default —
35
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Speed PID Switching Frequency
Program
Feedback
Feedback Settings
While running, this parameter establishes the threshold speed setting that is
used to determine if PID control may engage or remain engaged if active.
Direct Access Number — F466
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
V/I Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the
V/I
input terminals.
Note:
See note on
for additional information on the
V/I
terminal.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
Direct Access Number — F470
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......