P9 ASD Installation and Operation Manual
167
Stall Prevention During Regeneration
Program
Protection
Stall
The function of this parameter is to disable the
Over-Voltage
Stall
(
and
the
Over-Current Stall
(
) function during regeneration only.
Application-specific conditions may occur that warrant disabling the
Stall
function during regeneration.
Settings:
0 — Disabled (Stall During Regenerative Braking)
1 — Enabled (No Stall During Regenerative Braking)
Direct Access Number — F453
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Time-Based Alternation Direct Mode Emergency Setpoint
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Direct
mode,
this parameter sets the
Virtual Linear Pump
setpoint.
Direct Access Number — F456
Parameter Type —
Numerical
Factory Default —
10
Changeable During Run —
Yes
Minimum —
Setting
Maximum —
Setting
Units — %
Current Control Proportional Gain
Program
Feedback
PG Settings
This parameter sets the sensitivity of the ASD when monitoring the output
current to control speed.
The larger the value entered here, the more sensitive the ASD is to changes in
the received feedback.
Direct Access Number — F458
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Speed Loop Proportional Gain
Program
Feedback
PG Settings
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the larger the change in the output speed for a
given received feedback signal.
Direct Access Number — F460
Parameter Type —
Numerical
Factory Default —
12
Changeable During Run —
No
Minimum — 1
Maximum — 9999
Speed Loop Stabilization Coefficient
Program
Feedback
PG Settings
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the quicker the response to changes in the
received feedback.
Direct Access Number — F461
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 1
Maximum — 9999
Load Moment of Inertia 1
Program
Feedback
PG Settings
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the
Drooping Control
mode.
Direct Access Number — F462
Parameter Type —
Numerical
Factory Default —
35
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......