Table 6. Discrete Input Terminal Assignment Selections and Descriptions.
*Sel. No.
Terminal Selection Descriptions
NO NC
0
1
Unassigned
— No operation.
2
3
Forward
— Provides a
Forward
run command.
4
5
Reverse
— Provides a
Reverse
run command.
6
7
Standby
— Enables the
Forward
and
Reverse
operation commands.
8
9
Reset
—
Resets
the device and any active faults.
10
11
Preset Speed 1
—
Preset Speed 1
is used as the
LSB
of the 4-bit nibble that is used to select a
Preset Speed
.
12
13
Preset Speed 2
—
Preset Speed 2
is used as the second bit of the 4-bit nibble that is used to select a
Preset Speed
.
14
15
Preset Speed 3
—
Preset Speed 3
is used as the third bit of the 4-bit nibble that is used to select a
Preset Speed
.
16
17
Preset Speed 4
—
Preset Speed 4
is used as the
MSB
of the 4-bit nibble that is used to select a
Preset Speed
.
18
19
Jog
— This terminal activates a
Jog
for the duration of the activation. The
Jog
20
21
Emergency Off
— Terminates the output signal from the ASD and may apply a brake if so configured. The braking
22
23
DC Braking
— The ASD outputs a DC current that is injected into the windings of the motor to quickly brake the
motor.
24
25
Accel/Decel Switching 1/Accel/Decel Switching 2
— Activating combinations of discrete input terminals
Accel/Decel Switching
1
and
2
allow for the selection of Accel/Decel profiles 1 – 4 as shown below.
See
for additional information on this terminal setting.
26
27
28
29
V/f Switching 1/V/f Switching 2
— Activating combinations of discrete input terminals
V/f Switching 1
and
2
allow for the selection of a V/f switching
profile as listed below.
30
31
NO/NC = Normally Open/Normally Closed.
*Selection numbers are used when configuring the ASD via communications. The Normally Open (NO) or Normally
Closed (NC) configuration must be chosen by selecting the associated number.
A/D SW Terminal
A/D Profile Selection
#1
#2
0
0
1
0
1
2
1
0
3
1
1
4
1=Terminal Activated
The settings of the A/D selections 1 – 4 are performed
at
/
/
, and
, respectively.
Accel/Decel
profiles are comprised of the
Accel/
Decel
settings,
Pattern
, and
Switching Frequency
.
V/f Switching Terminal
V/f Selection
#1
#2
0
0
1
0
1
2
1
0
3
1
1
4
1=Terminal Activated
The 1
–
4 settings of the V/f Switching
selections are performed at
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......