Deceleration Time 3
Program
Special
Accel/Decel 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the
Maximum Frequency
to 0.0 Hz for the
3 Deceleration
profile.
The Accel/Decel pattern may be set using
. The minimum Accel/Decel
time may be set using
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
deceleration times.
Direct Access Number — F511
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Acceleration/Deceleration Pattern 3
Program
Special
Accel/Decel 1 – 4 Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the
3 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F512
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Acceleration/Deceleration Switching Frequency 2
Program
Special
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel 2
profile to the
Accel 3
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F513
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Acceleration Time 4
Program
Special
Accel/Decel 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the
Maximum Frequency
for the
4 Acceleration
profile. The
Accel/Decel pattern may be set using
. The minimum Accel/Decel time
may be set using
.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
acceleration times.
Direct Access Number — F514
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......