P9 ASD Installation and Operation Manual
177
Acceleration/Deceleration Pattern 1
Program
Special
Accel/Decel 1 – 4 Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the
1 Accel/Decel
parameters (see
and
).
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
The figures below provide a profile of the available accel/decel patterns.
Direct Access Number — F502
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Linear
acceleration and deceleration is the
default pattern and is used on most
applications.
S-pattern 1
is used for applications that
require quick acceleration and deceleration.
This setting is also popular for applications
that require shock absorption at the start of
acceleration or deceleration.
S-pattern 2
decreases the rate of change
above the base frequency for acceleration
and deceleration.
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......