208
P9 ASD Installation and Operation Manual
MON 1 Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
MON1
terminal.
Set the assigned function of
to zero and then set this parameter to a zero
output.
See
for additional information on this parameter.
Direct Access Number — F690
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — 100.0
Units — %
MON 2 Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to set the output signal type of the
MON2
output
terminal.
See
for additional information on this parameter.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number — F691
Parameter Type —
Selection List
Factory Default —
0 – 10V
Changeable During Run —
Yes
MON 2 Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
MON2
output terminal.
The
MON2
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F692
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
MON 2 Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
MON2
terminal.
Set the assigned function of
to zero and then set this parameter to a zero
output.
See
for additional information on this parameter.
Direct Access Number — F693
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Panel Parameter Write Lock Out
Program
Utilities
Prohibition
This parameter is not used with the P9 ASD.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F700
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......