ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
89
Commissioning
6
6.1
PROFIBUS DP
6.1.1
Commissioning the DP slave
Software requirements
Table 6- 1
Software prerequisites for commissioning
Configuration software
used
Version
Explanations
STEP 7
–
Configure the IM 153-x from the
STEP 7
hardware catalog, then the
unrestricted S7 functionality is available (e.g removal / insertion
interrupts to the DP master with "Module change during operation"
or forwarding the configuration data to the FM or HART modules)
If your IM 153-x version is not in the hardware catalog, then
integrate the GSD file in
STEP 7
.
COM PROFIBUS
≥ Version 3.0
You have integrated the IM 153-x with the GSD-file in the
COM PROFIBUS
.
COM PROFIBUS
supports the GSD-file up to revision 2.
You can use the GSD-file revision ≥ 3 for the configuration, however
then the new functions of the IM 153-2Bx00 and the IM 153-2Bxx1
are not supported.
1
Configuration software to
the used DP master
–
You integrate the GSD file of the DP slave.
1
Refer to chapter "PROFIBUS DPV1 operation (Page 95)" to find out which functions can be operated with the individual
GSD revisions.
For the current GSD file, go to Internet
(
http://support.automation.siemens.com/WW/view/en/113498
).
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...