![Siemens IM 153-4 PN Скачать руководство пользователя страница 231](http://html.mh-extra.com/html/siemens/im-153-4-pn/im-153-4-pn_operating-instructions-manual_377175231.webp)
Technical Specifications
10.2 Parameters of the IM 153-x
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
229
Use in residential areas
If you use the ET 200M in residential areas, you must ensure that the radio interference
emissions comply with limit value class B in accordance with EN 55011.
The following measures are recommended to ensure the interference complies with limit
value class B:
●
Install the ET 200M in grounded switching cabinets/boxes
●
Use of noise filters in the supply lines
WARNING
There is a risk of injury or of damage to assets.
In potentially explosive environments, there is a risk of injury or damage if you
disconnect any connectors while the ET 200M is in operation.
In explosive environments, always isolate the ET 200M before you disconnect
connectors.
Laser protection classes authorization (for the IM 153-2 FO)
Class 1 in accordance with EN 60825-1: 1994+A11: 1996 or IEC 60825-1: 1993 including
amendment 1:1997
In the case of an intentional / unintentional opening of the accessible FOC radiation in
accordance with degree of endangering 1 as per EN 60825-2: 1994 or IEC 60825-2: 1993.
10.2
Parameters of the IM 153-x
Parameter assignment
You configure the IM 153-x or the ET 200M with
STEP 7 or COM PROFIBUS. If you use a
different configuration tool, you must integrate the GSD file.
Table 10- 2 Parameters of the IM 153 x
Parameters
Range of values
Default
Scope
DPV1 mode
block / enable
enable
ET 200M
Start up at preset ≠ actual
configuration?
yes/no
No
ET 200M
"Module change during
operation"?
yes/no
No
ET 200M
Diagnostic Interrupt
block / enable
enable
ET 200M
Process interrupt
block / enable
enable
ET 200M
Removing / insertion interrupt
block / enable
enable
ET 200M
Analog-value format
SIMATIC S7 / SIMATIC S5
SIMATIC S7
ET 200M
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...