Connecting
5.4 Wiring the power supply and modules
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
79
5.4.2
Wiring the Power Supply and IM 153-x
Power Cables
Use flexible cables to wire the power supply.
If you use only one cable per connection, you don't need an end ferrule.
Jumper
Use the jumper to wire the power supply module PS 307 with the IM 153-x. The jumper
comes with the power supply module.
Further 24 V connections
On the power supply PS 307 via the jumper an additional 24 V-connections are still free for
connecting the supply of the S7-300 modules.
Wiring the 24 V connections with redundant configuration with 2 x IM 153-2
Note
If, in a configuration for redundancy, you connect the supply voltage L+ when wiring to the
IM 153-2, this brings about a short circuit via the ground terminal.
Reason: The two IM 153-2 have a mutual ground cable via the BM IM /IM bus module.
with IM 153-2AA02 / -2AB01:
We recommend, with a redundant configuration, that you protect the L+-supply from the
IM 153-2 with 2.5 A.
with IM 153-2Bx00 / -2Bxx1:
•
In configurations with ungrounded reference potential (jumper between M and functional
ground removed, see the figure in the "Configuration of an ET 200M with ungrounded
reference potential (Page 54)" chapter), in the case of a polarity reversal an internal
electronic fuse is triggered and this regenerates after approx. 30 seconds.
•
With a configuration with grounded reference potential (bridge inserted between M and
functional earth) when connection this brings about a short circuit current via this bridge
and the functional earths.
In doing so, the IM 153-2 is not damaged if a protection is built in before the module
which is designed in accordance with the cross-section of the connection line.
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...