Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
203
Table 9- 9
Error type of the channel-related diagnostic - manufacturer-specific
Error type
Error text
Meaning
Remedy
10000
B
16
D
Parameter
configuration
error
Parameter configuration error, e.g.:
•
Module cannot evaluate the parameter (unknown,
inadmissible combination, ...)
•
Module not configured
•
User calibration does not correspond to the configuration
•
Calibration error
Correction of the
parameterization
10001
B
17
D
Encoder or load
voltage missing
The following voltages could me missing:
•
external supply voltage
•
Voltage to operate the module
Correction of the
process wiring
10010
B
18
D
Fuse faulty
The user´s exchangeable fuse has failed
Replace the fuse
10011
B
19
D
Communication
error
With F technology (PROFIsafe):
•
Error with the consecutive number (sign of life)
•
Error in the user data CRC
•
User data timeout
Check the
communication paths
10100
B
20
D
Ground error
Ground error, e.g.:
•
The permissible common mode voltage for isolated
channels has been exceeded
•
The M line is broken in the case of isolated channels
Correction of the
process wiring
10101
B
21
D
Reference
channel fault
Error on the reference channel
Replace the reference
channel module
10110
B
22
D
Hardware
interrupt lost
Hardware interrupt has become lost
Correction tuning of
program /
process / module
10111
B
23
D
Warning
There could be a warning, if limit values like:
•
Speed
•
Load current
are exceeded
Correction tuning of
program /
process / module
11000
B
24
D
Switch off
There could be a switch off:
•
Power switch is triggered on account of short circuit,
asymmetry, contact to earth
•
Thermistor triggered
•
Quick stop
•
fail-safe switch off
Remedy the cause of
switch off and
acknowledge
11001
B
25
D
fail-safe switch
off
Trigger / cause for fail-safe switch of is given
Remedy the cause of
switch off
11010
B
26
D
External error
External (process-side) error, e.g.:
•
Sensor error
•
Actuator error
•
Sensor data is incorrect
Replace sensor /
actuator / correct
process wiring
11011
B
27
D
Unclear error
Unclear errors are those that are not specified in any more
detail
different, depending on
cause of error
11100
B
28
D
reserved
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...