Technical Specifications
10.4 Technical specifications of the IM 153-4 PN interface module
ET 200M
238
Operating Instructions, 12/2008, EWA-4NEB780600602-08
Voltages, currents, potentials
Rated supply voltage of electronics (L+)
24 VDC
•
Incorrect polarity protection
yes
•
Voltage failure bypass
Min. 5 ms
Galvanic isolation
•
Between the backplane bus and electronic
components
No
•
Between Ethernet and electronic components yes
•
Between the supply voltage and electronic
components
No
Permissible potential difference (relative to rail)
75 VDC / 60 VAC
Insulation test voltage
500 VDC
Current consumption from rated supply voltage
(L+)
max. 600 mA
Current consumption from backplane bus
Max. 1.5 A
Power loss of the module
max. 6 W
Status, alarms, diagnostics
Interrupts
yes
Diagnostic function
yes
•
Group error
•
Bus monitoring PROFINET IO
Red LED "SF"
Red "BF" LED
•
Monitoring of the supply voltage of the
electronics
Green "ON" LED
•
Maintenance requirement (maintenance)
yellow "maint" LED
•
Existing connection to network
One green "LINK" LED per port
•
Transmitting / receiving data on the network
One yellow "RX/TX" LED per port
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...