![Siemens IM 153-4 PN Скачать руководство пользователя страница 204](http://html.mh-extra.com/html/siemens/im-153-4-pn/im-153-4-pn_operating-instructions-manual_377175204.webp)
Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
202
Operating Instructions, 12/2008, EWA-4NEB780600602-08
Channel-specific error messages
Table 9- 8
Error type of the channel-related diagnosis in accordance with the PROFIBUS standard
Error type
Error text
Meaning
Remedy
00000
B
0
D
reserved
00001
B
1
D
Short circuit
Short circuit, e.g.:
•
Sensor lines short circuited in accordance with P
potential
•
Sensor lines short circuited in accordance with M
potential
•
Output lines short circuited in accordance with P
potential
•
Output lines short circuited in accordance with M
potential
•
Output lines short circuited in accordance with ground
Correction of the
process wiring, M
circuit, P circuit
00010
B
2
D
Low voltage
Supply voltage is below the tolerance range
Correction on the
power supply, HART:
analog output current
established
00011
B
3
D
Overvoltage
Supply voltage is above the tolerance range
Correction on the
power supply
00100
B
4
D
Overload
the output stage is overloaded
Correction tuning of
module / actuator,
HART: analog output
saturated
00101
B
5
D
Excess
temperature
the output stage is overloaded and has become too hot
Correction tuning of
module / actuator
00110
B
6
D
Wire break
Wire break, e.g.:
•
Signal line to a sensor interrupted
•
Signal line from an actuator interrupted
•
Sensor power line interrupted
Correction of the
process wiring
00111
B
7
D
High limit
exceeded
Value is above the over range
Correction tuning of
module / actuator
01000
B
8
D
Low Limit
exceeded
Value is below the under range
Correction tuning of
module / actuator
01001
B
9
D
Fault
Error, e.g.:
•
Load voltage on output
•
Encoder supply
•
Hardware error in the module
•
Shield welded on or jammed
•
Life span of the switching element reached
Exchange the module
01010
B
to
01111
B
10
D
to
15
D
reserved
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...