Brief instructions on commissioning
2.2 Commissioning on PROFINET IO
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
31
SM 322: Short-circuit to L+
1.
Open the front panel of the DO-module and use a wire to short circuit the digital output 0
(terminal 3) after L+ (terminal 1).
2.
Note the status LEDs.
IM 153-2:
–
SF: ON
SM 322; DO 8 x DC 24 V/0,5 A:
–
SF: lights up → a diagnostic message is pending
–
F0: light up → channel error
–
0: OFF → Output is not active
3.
Evaluate the diagnostic message.
Result:
–
Station status 1 Byte x.3 is set → external diagnostics
–
Identifier-related diagnostics: Byte (x+7).4 is set → Slot 5
–
Channel-related diagnostics:
Byte (x+16).0 to (x+16).5: 000100
B
→ Slot 5
Byte (x+17).0 to (x+17).5: 000000
B
→ Channel 0
Byte (x+18).0 to (x+18).4: 00001
B
→ Short circuit
4.
Remove the wire between terminal 3 and terminal 1.
Evaluate the diagnosis LEDs once again.
IM 153-2:
–
SF: off
SM 322; DO 8 x DC 24 V/0,5 A:
–
SF: off
–
F0: off
–
0: On
The diagnostic message is deleted.
See also
Diagnosis with STEP 7 or STEP 5 (Page 188)
2.2
Commissioning on PROFINET IO
You will find further information on the PROFIBUS IO in the following manuals:
●
System Manual "PROFINET System Description
(
http://support.automation.siemens.com/WW/view/en/19292127
●
"From PROFIBUS DP to PROFINET IO
(
http://support.automation.siemens.com/WW/view/en/19289930
)" Programming Manual
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...