Connecting
5.2 Connecting PROFIBUS DP
ET 200M
72
Operating Instructions, 12/2008, EWA-4NEB780600602-08
●
up to 12 MBaud, with vertical cable departure
–
without PD jack (6ES7972-0BA12-0XA0)
–
with PD jack (6ES7972-0BB12-0XA0)
●
up to 12 MBaud, with diagonal cable departure
–
without PD jack (6ES7972-0BA41-0XA0)
–
with PD jack (6ES7972-0BB41-0XA0)
Connecting the Bus Connector
Proceed as follows to connect the bus connector:
1.
Plug the bus connector into the IM 153-x.
2.
Tightly screw the bus connector into the IM 153-x.
3.
If the bus connector is located at the start or end of a segment, you must connect the
terminating resistor (switch setting "ON").
Alternative: You use the PROFIBUS terminator as an active bus connector.
4.
Lay the bus cable(s) in the area intended for the IM 153-x to the right alongside the DC
24 V connection terminal.
Ensure that the nodes to which the terminating resistor is connected are always supplied
with voltage during power-up and operation.
5.2.2
Connecting the Fiber-Optic Cable to the IM 153-2 FO
Required accessories
●
Packaging with Simplex connectors and polishing sets (6GK1901-0FB00-0AA0)
●
Packaging with plug adapters (6ES7195-1BE00-0XA0)
●
Tool for removing the cable sheath (6GK1905-6PA10)
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...