Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
204
Operating Instructions, 12/2008, EWA-4NEB780600602-08
Error type
Error text
Meaning
Remedy
11101
B
29
D
Error 1 in
actuator /
sensor
Error 1 in a an HMI device that is connected to a module.
Correction in actuator /
sensor depending on
error message, HART:
Primary value outside
of limits
11110
B
30
D
Error 2 in
actuator /
sensor
Error 2 in a an HMI device that is connected to a module.
Correction in actuator /
sensor depending on
error message, HART:
Secondary value
outside of limits
11111
B
31
D
Channel
temporarily
unavailable
e.g. due to calibration, firmware update, manual mode, etc. Different, depending
on the cause;
e.g., wait until the
initiated function
(calibration, FW
update) is finished.