ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
129
Functions
8
8.1
Support for I/O modules with expanded input data
The IM 153-2BAx2 interface module supports I/O modules with expanded input data
(> 16 bytes). For more detailed information, refer to the documentation on the respective
modules.
Expanded output data are not supported.
For the ET 200M, this means that:
●
The I/O module in use must support provision of expanded input data.
●
The IM 153-2BAx2 supplies the substitute value "0" in the expanded input data of an I/O
module that is starting up or that has been removed.
●
The total amount of input data must not exceed the following values:
–
128 bytes per slot
–
244 bytes per IM 153-2BAx2. i.e., per ET 200M
These limits are checked during configuration.
●
"Standard" and expanded input data are internally consistent but not consistent relative to
each other.
The following figure illustrates this point.
%\WH
%\WH
%\WH
%\WH
%\WH
%\WH
%\WH
XSWR
PD[
E\WH
ಯ6WDQGDUGರLQSXWGDWD
DOOE\WHVDUHFRQVLVWHQW
6XEVWLWXWHYDOXHVDUHGHWHUPLQHG
IURPWKHPRGXOHW\SH
HJ)))
+
IRUDQDORJ
VLJQDOPRGXOHV
&RQVLVWHQF\OLPLW
([SDQGHGLQSXWGDWD
DOO[E\WHVDUHFRQVLVWHQW
7KHVXEVWLWXWHYDOXHVDUHಯರ
The expanded input data are updated in longer time intervals than the "standard" input
data.
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...