Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
186
Operating Instructions, 12/2008, EWA-4NEB780600602-08
LEDs
SF
BF
ON
Meaning
Remedy
on
off
on
inadmissible PROFIBUS address
Is the SF LED of an SM / FM also lit?
•
If so: Error or diagnosis in an S7 300
module
•
If not: IM 153-1 is faulty.
On the IM 153-1 set a valid PROFIBUS address (1
to 125)
Check the SM / FM with the diagnostics. Replace
the S7-300 module or the IM 153-1 or contact your
Siemens representative.
off
off
on
There is data exchange between the DP
master and the ET 200M.
The preset configuration and actual
configuration of the ET 200M match.
—
* not relevant
Status and error displays of the IM 153-2
6)
%)
21
6)
%)
$&7
$&7
21
,0$$$%
,0%[
6)
%)
$&7
21
,0%[[
%)
216XSSO\YROWDJH*UHHQ
DYDLODEOH
$&70RGXOHDFWLYH<HOORZ
RQO\LQUHGXQGDQWPRGH
%)b(UURURQWKHXQGHUODLGEXV5HG
LUUHOHYDQWIRU(70
%)%)(UURURQWKH352),%86'35HG
6)*URXSHUURU5HG
Table 9- 2
LEDs
SF
BF /
BF1
ACT
ON
Meaning
Remedy
off
off
off
off
No voltage on the IM 153-2 or there is a
hardware fault with the IM 153-2.
Switch on the power supply module or
replace the IM 153-2.
*
*
*
on
There is voltage on the IM 153-2.
IM 153-2 is functioning.
—
on
off
off
off
IM 153-2 is undergoing a hardware reset
after switching on
—
on
on
on
on
Hardware test after switching on
—
on
on
off
off
The operating system update is running
—
off
flashes
at
0.5 Hz
off
off
The operating system update has
concluded successfully
with IM 153-2Bx00:
remove the SIMATIC Micro Memory
card and switch off the IM 153-2.
on
flashes
at
0.5 Hz
off
off
external error, e.g. unsuitable operating
system or SIMATIC Micro Memory card
Use a suitable operating system for the
update.
Do not remove the SIMATIC Micro
Memory card during the update (only
with IM 153-2Bx00).
on
flashes
at
2 Hz
off
off
internal error, e.g. when writing the update
files
Repeat the update process.
If the LEDs indicate an error, the
internal memory is faulty.
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...