6.6.2
LIST Parameters
The following parameters are available in each transient list step.
PARAMETER
Range
1
Unit
Description
#
1 - 199
-
Displays the row number in the
transient table. These numbers are
generated automatically.
Ramp
0.1 –
10,000,000
msec.
Ramp time to slew from existing set
point to new set point value. Applies
to both Frequency and Voltage.
If previous set value is the same as
new value, the value is not slewed
but rather stays at the same value for
the duration of the ramp time.
Frequency
15 – 5000
Hz
New frequency value
Voltage AC
1
0 – 135
V rms
New AC voltage value
Dwell
0.1 -
10,000,000
msec.
Dwell time. At the end of the ramp
time, the new set values remain in
effect during the dwell period. At the
end of the dwell time, the next list
entry (if any) will be executed.
Table 6-7: Available Transient List Parameters
Note 1:
Range may differ on models with Transformer (T) option