LMX SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 275 of 463
Query Syntax
[SOURce:]PROTect[:RMS]:POWer:TDELAY:DEFault?
Description
This command returns the default true power protection trip delay
time setting.
Query Example
PROT:POW:TDELAY:DEF?
5
Query Syntax
[SOURce:]PROTect[:RMS]:POWer:TRIPped?
Description
This command returns the true power protection trip status. Returns
1 if tripped or 0 if not.
Query Example
PROT:POW:TRIP?
41.667
Command Syntax
[SOURce:]PROTect[:RMS]:POWer:TRIPped:CLEar
Description
This command clears the true power protection trip status. Once
cleared, the power source output can be enabled.
Parameters
None
Parameter Format
n/a
Example
PROT:POW:TRIP:CLE
Command Syntax
[SOURce:]PROTect[:RMS]:KVA[:STATe] <ON|OFF>
Description
This command turns the apparent power protection on or off.
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b> | <cr>
Example
PROT:POW ON
Query Format
[SOURce:]PROTect[:RMS]:KVA[:STATe]?
Returned Data Format
<b>
Query Example
PROT:KVA?
1
Command Syntax
[SOURce:]PROTect[:RMS]:KVA:LEVel <LEVEL>
Description
This command sets the apparent power protection trip level. Setting
is in KW.
Parameters
< LEVEL >
Parameter Format
<nr2>
Example
PROT:POW:LEV 5
Query Format
[SOURce:]PROTect[:RMS]:KVA:LEVel?
Returned Data Format
<b>
Query Example
PROT:KVA:LEV?
5.000
Query Syntax
[SOURce:]PROTect[:RMS]:KVA:LEVel:MINimum?
Description
This command returns the minimum apparent power protection level
setting.
Query Example
PROT:KVA:LEV:MIN?
0.000