5.10
Air Intake Filter Removal and Cleaning
Units equipped with a removable air intake filter must have their filter material cleaned on a
regular basis. A six-month cleaning interval is recommended. For units deployed in
particularly dirty environments, this cleaning interval should be shortened to three months
or less to prevent the air filter from clogging up with dirt. This applies to both Master units
and Auxiliary units.
Figure 5-7: Air Intake Filter Removal
5.10.1
Air Filter Removal
To remove the air filter, proceed as follows:
1.
Turn the unit off first. Using a small Philips screwdriver
2.
Remove the four Philips screws from the corners of the filter panel on the front of
the unit.
3.
Pull the filter panel toward you carefully and remove the filter material.
5.10.2
Filter Cleaning
Use warm water and some mild detergent to rinse all dirt out of the filter material. Allow
the filter do dry for 2 hours or more till fully dry before re-installing. If the filter material is
too dirty to clean, replace with a new filter. Contact customer service for replacement
filters.
5.10.3
Air Filter Installation
To reinstall the filter material, proceed as follows:
1.
Place the cleaned filter material against the lower part of the units front panel.
2.
Line up the filter so the filter corners align with the four corners of the filter space.
3.
Install the removable filter panel using the four screws.