LMX SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 269 of 463
Command Syntax
[SOURce:]PROTect:PEAK:VOLTage:LEVel <VOLTAGE LEVEL>
Description
This command sets the maximum voltage peak level. If the output
voltage peak exceeds the programmed peak level by more than this
amount, an error is tripped.
Parameters
<VOLTAGE LEVEL>
Parameter Format
<nr2>
Example
PROT:PEAK:VOLT:LEV 120.0
Query Format
[SOURce:]PROTect:PEAK:VOLTage:LEVel?
Returned Data Format
<nr2>
Query Example
PROT:PEAK:VOLT:LEV?
500.000
Query Syntax
[SOURce:]PROTect:PEAK:VOLTage:LEVel:MINimum?
Description
This command returns the minimum voltage peak level setting.
Query Example
PROT:PEAK:VOLT:LEV:MIN?
0.000
Query Syntax
[SOURce:]PROTect:PEAK:VOLTage:LEVel:MAXimum?
Description
This command returns the maximum voltage peak level setting
Query Example
PROT:PEAK:VOLT:LEV:MAX?
500.000
Query Syntax
[SOURce:]PROTect:PEAK:VOLTage:LEVel:DEFault?
Description
This command returns the default voltage peak level setting
Query Example
PROT:PEAK:VOLT:LEV:DEF?
500.000
Query Syntax
[SOURce:]PROTect:PEAK:VOLTage:TRIPped?
Description
This command returns 1 if the voltage peak protection has been
tripped or 0 if no trip occurred.
Query Example
PROT:PEAK:VOLT:TRIP?
0.000
Command Syntax
[SOURce:]PROTect:PEAK:VOLTage:TRIPped:CLEar
Description
This command clears the peak voltage protection trip status. Once
cleared, the power source output can be re-enabled.
Parameters
<VOLTAGE LEVEL>
Parameter Format
<nr2>
Example
PROT:PEAK:VOLT:TRIP:CLE