LMX SERIES™ OPERATION MANUAL
SECTION 4: Technical Specifications
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 25 of 463
4
Technical Specifications
Technical specifications shown here apply at an ambient temperature of 25° C ± 5° C.
4.1
Available Models – Power & Voltage Ranges
LMX Series models are available with either single-phase output configuration or three-
phase output configuration. The first digit of the model number identifies the output
configuration:
1
xxLMX = Single-phase
3
xxLMX = Three-phase
4.1.1
Single Phase Models – Direct Coupled Output
MODEL Rated
Power
(VA)
1
Output
Form
2
Output Voltage Max
3
(l-n/l-l)
Output Current
4
(A
rms
)
Input
Power
5
105LMX
500
1/2
0-135/270
4/2
1Ø
108LMX
750
1/2
0-135/270
6/3
1Ø
112LMX
1200
1/2
0-150/300
10/5
1Ø
140LMX
4000
1/2
0-135/270
32/16
3Ø
160LMX
6000
1/2
0-135/270
48/16
3Ø
4.1.2
Single Phase Models – Transformer Output
MODEL Rated
Power
(VA)
1
Output
Form
2
Output Voltage Max
3
(l-n/l-l)
Output Current
4
(A
rms
)
Input
Power
5
Direct
Transformer
Direct
Transformer
Ratio
1.5:1
Ratio
2.0:1
Ratio
2.5:1
Ratio
1.5:1
Ratio
2.0:1
Ratio
2.5:1
105LMXT
500
1/2
0-135/
270
0-202/
404
0-270/
540
0-338/
600
4/2
2.6/
1.3
2/
1
1.6/
0.8
1Ø
108LMXT
750
1/2
0-135/
270
0-202/
404
0-270/
540
0-338/
600
6/3
4/
2
3/
1.5
2.4/
1.2
1Ø
140LMXT
4000
1/2
0-135/
270
0-202/
404
0-270
/540
0-338/
600
32/16
21.3/
10.7
16/
8
12.8/
6.4
3Ø
160LMXT
6000
1/2
0-135/
270
0-202/
404
0-270/
540
0-338/
600
48/16
32/
10.7
24/
8
19.2/
6.4
3Ø