LMX SERIES® OPERATION MANUAL
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 64 of 463
Models 105LMX, 108LMX, 112LMX, 305LMX, 308LMX, 312LMX and 320LMX are supplied
with an AC input power cord. Install an appropriate plug onto the end of the power cord
and connect to the proper outlet. Refer to Section 4.8 for recommended input service of
the configured input voltage form.
Wire Color
( US Models )
Wire Color
( CE Models )
SINGLE PHASE
LINE ( HI )
Black
Brown
NEUTRAL ( LO )
White
Blue
GROUND ( CHS )
Green
Green/Yellow
THREE PHASE
LINE 1 ( L1 or A )
Black
Brown
LINE 2 ( L2 or B )
White
Black
LINE 3 ( L3 or C )
Red
Grey
GROUND ( CHS )
Green
Green/Yellow
The input power of Models 140LMX, 160LMX, 345LMX and 360LMX is connected to the
Input Power Terminal Block located on the rear panel of the power source. In this case, the
input wiring is brought to this terminal block from the distribution panel. The connection
points are labeled "A," "B," "C," "N," and "CHS."
The input wiring is connected to these points in the appropriate order with CHS being the
safety ground or earth potential. The LMX-Series Power Sources are not sensitive to phase
rotation of the input voltage. For all standard DELTA input voltage forms (208, 220, and
240VAC) and WYE input voltage forms (220/380VAC, 230/400VAC 240/416VAC, and
277/480VAC), the "N" (Neutral) terminal is not used. Refer to Figure 5-6 for the proper wire
size to be used with the configured input power form.
Note:
It is the user's responsibility to meet all local and national electrical codes when
installing this equipment.