LMX SERIES® OPERATION MANUAL
SECTION 4: Technical Specifications
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 40 of 463
OUTPUT
SPECIFICATION
Accuracy
15-45Hz, ± 0.25% of F.S.
45-500 Hz, ±0.1% F.S.
20-5,000 Hz, ± 0.5% F.S.
Current Protection (CP)
Modes
Constant Current (CC)
or Output Trip (CV)
Current Overload Mode
Allows 150% of max. RMS current for up to 1 min
Phase Angle
(In 3 and 2 Phase Mode)
Programmable Phase (B, C)
0 - 359.9°
Resolution
0.1°
Accuracy
±0.35° / ±0.1° in Phase Reg. Mode
Programmable Impedance (Real-Time Mode)
Resistance (R)
See
Inductance (L)
Programmable Impedance (RMS Mode)
Resistance (R)
See
Inductance (L)
4.4.1
Programmable Output Impedance Ranges by Phase Mode
The programmable range for output impedance varies based on model, phase mode setting
and number of units connected in parallel in Master/Aux mode. The table below
summarizes the available ranges as function of these.
± Limits
0 - Max Limits
± Limits
0 - Max Limits
Models
Phase Mode
Real Time R
+/- Ohms
Real Time L +
µ
H
RMS R +/-
Ohms
RMS L +
µ
H
105LMX, 108LMX, 112LMX,
140LMX, 160LMX
Split Phase
200.000
100.000
200.000
100.000
Single Phase
100.000
50.000
100.000
50.000
305LMX, 308LMX, 312LMX,
320LMX, 345LMX, 360LMX
Three Phase
100.000
50.000
100.000
50.000
Split Phase
200.000
100.000
200.000
100.000
Single Phase
100.000
50.000
100.000
50.000
Parallel Systems - 2 Units
Three Phase
50.000
25.000
50.000
25.000
Split Phase
100.000
50.000
100.000
50.000
Single Phase
50.000
25.000
50.000
25.000
Parallel Systems - 3 Units
Three Phase
33.333
16.667
33.333
16.667
Split Phase
66.666
33.333
66.666
33.333
Single Phase
33.333
16.667
33.333
16.667
Parallel Systems - 4 Units
Three Phase
25.000
12.500
25.000
12.500
Split Phase
50.000
25.000
50.000
25.000
Single Phase
25.000
12.500
25.000
12.500
Parallel Systems - 5 Units
Three Phase
20.000
10.000
20.000
10.000
Split Phase
40.000
20.000
40.000
20.000