LMX SERIES™ OPERATION MANUAL
SECTION 12: Warnings & Error Messages
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 448 of 463
Error Source
Code
Category Error Message
Possible Cause
Resolution
Front panel
358
Internal
Error
Did not receive MDO 1 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
359
Internal
Error
Did not receive MDO 2 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
360
Internal
Error
Did not receive MDO 3 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
361
Internal
Error
Did not receive MDO 4 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
362
Internal
Error
Did not receive MDO 5 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
363
Internal
Error
Did not receive MDO 6 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
364
Internal
Error
Did not receive MDO 7 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
365
Internal
Error
Did not receive MDO 8 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
366
Internal
Error
Did not receive MDO 9 -
Controller A.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
367
Internal
Error
Did not receive MDO 10 -
Controller A.
An inconsistency was
detected in the power
Turn unit off, check
parallel cable connections
if present and then turn