LMX SERIES® OPERATION MANUAL
SECTION 4: Technical Specifications
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 44 of 463
4.10
AC Input Power Requirements
This paragraph lists and defines the input voltage forms that are accepted by the various
models within the LMX-Series model range. Each model is listed separately. Refer to the
appropriate model when determining proper input service requirements. The input
currents listed are for operation at full rated load. Overload conditions will result in higher
input currents that still fall within the recommended input service.
The input power transformer of the LMX-Series Power Source has taps for each of the listed
power forms - one of which is selected by the factory at time of order. Once selected, the
unit will operate at designated voltage, ±10%.
4.10.1
105LMX AC Input
The Model 105LMX single-phase input voltages, required input currents at full rated load
and recommended service input currents are stated as below.
NO
INPUT VOLTAGE
INPUT CURRENT
RECOMMENDED SERVICE
1
100 Vac ±10%, 47-63 Hz
12 Arms
25 A
2
110 Vac ±10%, 47-63 Hz
12 Arms
25 A
3
120 Vac ±10%, 47-63 Hz
11 Arms
25 A
4
200 Vac ±10%, 47-63 Hz
6 Arms
15 A
5
208 Vac ±10%, 47-63 Hz
6 Arms
15 A
6
220 Vac ±10%, 47-63 Hz
6 Arms
15 A
7
230 Vac ±10%, 47-63 Hz
6 Arms
15 A
8
240 Vac ±10%, 47-63 Hz
6 Arms
15 A
4.10.2
108LMX AC Input
The Model 108LMX single-phase input voltages, required input currents at full rated load
and recommended service input currents are stated as below.
NO
INPUT VOLTAGE
INPUT CURRENT
RECOMMENDED SERVICE
1
100 Vac ±10%, 47-63 Hz
17 Arms
25 A
2
110 Vac ±10%, 47-63 Hz
16 Arms
25 A
3
120 Vac ±10%, 47-63 Hz
15 Arms
25 A
4
200 Vac ±10%, 47-63 Hz
9 Arms
25 A
5
208 Vac ±10%, 47-63 Hz
9 Arms
25 A
6
220 Vac ±10%, 47-63 Hz
8 Arms
15 A
7
230 Vac ±10%, 47-63 Hz
8 Arms
15 A
8
240 Vac ±10%, 47-63 Hz
8 Arms
15 A