LMX SERIES™ OPERATION MANUAL
SECTION 12: Warnings & Error Messages
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 442 of 463
Error Source
Code
Category Error Message
Possible Cause
Resolution
Front panel
101
Error
AC voltage set point
cannot change due to
user limit.
Setting conflict. Setting
outside of User Limits
Check setting
Front panel
102
Error
DC voltage set point
cannot change due to low
range.
Setting conflict. Setting
outside of User Limits
Check setting
Front panel
103
Error
AC voltage set point
cannot change due to low
range.
Setting conflict. Setting
outside of User Limits
Check setting
Front panel
104
Error
Waveform change in
progress.
Waveform change in
progress
Wait
Front panel
105
Error
Error changing service
name
Internal Service Error.
Could not change service
Try recycling power. If
error persists, contact
customer service
Front panel
106
Error
Error getting service
name
Internal Service Error.
Could not get service
name
Try recycling power. If
error persists, contact
customer service
Front panel
109
Error
Transient step mode not
available on UPC
compatible mode.
Setting conflict. Step
mode only supported in
LMX mode.
Switch to LMX mode or
use Segments
Front panel
110
Error
System is about to
reboot.
Warning, Reboot
imminent
Wait
Front panel
111
Error
Cannot reboot system.
Soft reboot failed. Front
panel could not reboot
itself.
Try recycling power. If
error persists, contact
customer service
Front panel
115
Error
Unable to renew the
DHCP lease. Changing to
Auto-IP mode.
LAN Error. IP address
lease from DHCP expired
Renew IP lease of use
Auto IP mode
Front panel
116
Error
Failed starting firmware
update.
Firmware Update Error.
Unable to start firmware
update
Check for correct
firmware image file and
version.
Front panel
117
Error
Unable to execute this
action with output
enable.
Setting conflict.
Requested action not
possible with output ON
Turn output OFF
Front panel
118
Error
Frequency set point
cannot change due to
waveform saturation.
Setting conflict. In
extended voltage range,
frequency range is
restricted. Max peak
voltage is reduced
outside this range and if
there is a DC offset
programmed, the peak of
the voltage exceeds the
max. limit.
Reduce programmed
RMS and/or DC value.
Front panel
119
Error
Frequency set point
cannot change due to
user limit.
Setting conflict.
Frequency set point
outside User Limits
Change User Limits or
frequency setting
Front panel
120
Error
Frequency not allowed in
"DC mode".
Setting conflict. No
frequency setting applies
in DC mode
Change to AC or AC+DC
mode
Front panel
121
Error
Waveform set point
cannot change due to
waveform saturation.
Setting conflict. The crest
factor of the waveform
selected would result in a
peak voltage that exceeds
the max peak voltage
supported. Or combined
AC peak + DC
Reduce waveform crest
factor ratio or reduce
programmed RMS and/or
DC value.