![Omron CS1W-NC113 - REV 02-2008 Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/omron/cs1w-nc113-rev-02-2008/cs1w-nc113-rev-02-2008_manual_742370047.webp)
3-4
Section
Wiring
34
In this example, a 5-VDC photocoupler input motor drive is used for outputting
CW and CCW pulses.
Position Control Unit
(open collector output)
24-VDC
input
CW pulse
output
CCW pulse
output
1.6 k
Ω
1.6 k
Ω
A1/B1
+
--
+
--
+
--
Motor drive (for 5-VDC input)
Approx.
12 mA
Approx.
12 mA
A8/B8
A6/B6
24-VDC
power
supply
(For example R=220
Ω
)
A2/B2
Note
In this example, the 1.6 k
Ω
resistors of the PCU are used to allow a 24-VDC
power supply to be used with a motor drive rated at 5 VDC.
When wiring your system, carefully note the current required by the motor drive
in order to avoid damaging the input circuitry of the motor drive.
Outputting CW and CCW
Pulses, Example 1