![Omron CS1W-NC113 - REV 02-2008 Скачать руководство пользователя страница 204](http://html1.mh-extra.com/html/omron/cs1w-nc113-rev-02-2008/cs1w-nc113-rev-02-2008_manual_742370204.webp)
8-8
Section
Timing Chart for Memory Operation
194
Ladder Program
The work bit R1 is used to start write.
DIFU
R1
MOV
012C
D00500
200814
MOV
#000E
D00501
MOV
#0000
D00502
R1
Write switch
Work bit
Data Transferring
Flag
MOV
#1000
D00503
200112
Sets the total number of
write words. In this case,
sets to 12C (Hex).
(100 positioning sequences
×
3 words = 300 words)
Sets the area in the CPU Unit
used to set the positioning
sequences (EM Area, bank 0).
Set the beginning word of the
area in the DM or EM Area used
to set the positioning sequences.
In this case, sets to 0000.
Sets the beginning address of the
area in the PCU to which the
positioning sequences are to be
written. In this case, sets to 1000.
WRITE DATA
Operating data area
D00500
D00501
D00502
D00503
012C
000E
0000
1000
Write source area
Number of write words
Write destination address
Write source word
Positioning sequences (set in EM Area, bank 0)
E00000
E00001
E00002
:
E00297
E00298
E00299
Sequence #0
(3 words)
Sequence #99
(3 words)
:
200112
8-8
Timing Chart for Memory Operation
This section provides timing charts showing START and INDEPENDENT
START execution. The X axis is used as an example. It is first necessary to
understand the functions of the Busy Flag and the Sequence Number Enable
Bit.
8-8-1 Busy Flag
Turns ON while axes are outputting pulses. Turns OFF when execution is com-
pleted. No new start can be executed while the Busy Flag is ON.
8-8-2 Sequence Number Enable Bit
The Sequence Number Enable Bit is used when designating the sequence num-
ber for starting operation. Execution begins from the specified sequence num-
Содержание CS1W-NC113 - REV 02-2008