11.6.31 Error 32: PROFIBUS/PROFINET error
11.6.31.1 Error 32-1 (emergency code 8100h)
Cause: Profibus/Profinet option: process data timeout
Suggested steps:
This is possibly an EMC
issue. This is very likely if the
problem occurs when
switching on motor control
and/ or when connecting DC
link power supply.
l
Please check the device cabling for proper
connection.
l
Please check device grounding, i. e. the
connection to a metal backplane and cabinet
connection to earth.
l
Check motor grounding and motor cable
length.
The device was probably
disconnected from the
master controller, or the
master is overloaded.
l
Please check the bus system connection. Try
to replace the cables.
l
Please try to reduce computational load on the
master.
l
Try to increase the master cycle time.
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
403
11 Alarms & warnings
11.6.31.2 Error 32-2 (emergency code 8100h)
Cause: Profinet IRT: No firmeware on Profinet option available!
Suggested steps:
This is probably a software
issue.
l
Please try to switch to a different version of
device firmware.
l
Save your dataset and reset the axis module to
factory setting. See if the error persists, or if it
comes with activating a certain feature.
This is possibly a hardware
issue
If other measures fail to solve the problem, please
replace the servo drive.
11.6.31.3 Error 32-3 (emergency code 8100h)
Cause: Profinet IRT: sign of life fault!
Suggested steps:
This is possibly an EMC
issue. This is very likely if the
problem occurs when
switching on motor control
and/ or when connecting DC
link power supply.
l
Please check the device cabling for proper
connection.
l
Please check device grounding, i. e. the
connection to a metal backplane and cabinet
connection to earth.
l
Check motor grounding and motor cable
length.
The device was probably
disconnected from the
master controller, or the
master is overloaded.
l
Please check the bus system connection. Try
to replace the cables.
l
Please try to reduce computational load on the
master.
l
Try to increase the master cycle time.