11.6.14.13 Error 13-13 (emergency code FF00h)
Cause: Sercos option: Watchdog failure
Suggested steps:
SERCOS controller hardware watchdog. Please check the settings in the master!
The device was probably
disconnected from the
master controller, or the
master is overloaded.
l
Please check the bus system connection. Try
to replace the cables.
l
Please try to reduce computational load on the
master.
l
Try to increase the master cycle time.
11.6.14.14 Error 13-14 (emergency code FF00h)
Cause: Sercos option: Error in parameter data
Suggested steps:
This issue is probably
caused by an unsuitable
parameter setting.
l
Save your parameter set for a later restore.
l
See 'history of parameter changes' and undo
the latest changes.
l
Please check your parameter set for
implausible settings.
l
Please set device to factory setting, restart, and
see if the error occurs again.
l
When reporting this error to your service
partner, please include your device's
parameter setting.
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
351
11 Alarms & warnings
11.6.14.15 Error 13-15 (emergency code FF00h)
Cause: Sercos option: Communication error
Suggested steps:
Error in the topology detection. Topology not stable or not detected. Please check
the wiring!
This is possibly an EMC
issue. This is very likely if the
problem occurs when
switching on motor control
and/ or when connecting DC
link power supply.
l
Please check the device cabling for proper
connection.
l
Please check device grounding, i. e. the
connection to a metal backplane and cabinet
connection to earth.
l
Check motor grounding and motor cable
length.