B-44
BOP-1K 091719
B.180 SYSTem:VERSion? QUERY
SYST:VERS?
Syntax
:
Short Form: SYST:VERS?
Long Form: SYSTem:VERSion?
Return Value: <int_value>.<int_value> (YYYY.V)
Description:
Identifies SCPI Version implemented.
Returns SCPI Version number
:
YYYY = year, V = Revision number for specified year. (See example, Figure B-14.
FIGURE B-14. USING SYSTEM COMMANDS AND QUERIES
B.181 TRIGger:SOURce COMMAND
TRIG:SOUR
Syntax:
Short Form: TRIG:SOUR {BUS | EXT | IMM}
Long Form: TRIGger:SOURce {BUS | EXT | IMM}
Description:
Selects the active trigger source.
When TRIG:SOUR BUS is set, an event trigger is created by
sending either *TRG or GPIB <GET> commands. When TRIG:SOUR EXT is set, the trigger is created
by connecting the external trigger line (J2, pin 4 or pin 3 of the mating connector for J2) to analog sig-
nal ground (J2, pin 1 or J2 mating connector, pin 1). The trigger must be armed by sending either
INIT:IMM or INIT:CONT enable (ON) commands prior to sending the selected trigger command. (see
PAR. A.16). Receipt of the active trigger causes the power supply to program to the previously stored
values of VOLT:TRIG and CURR:TRIG (actual output voltage/current is dependent upon the load).
Sending TRIG:SOUR IMM causes the next VOLT:TRIG or CURR:TRIG to immediately program the
output, regardless of trigger arming. *RST sets TRIG:SOUR to BUS. Related Commands: <GET>,
*TRG, INIT:IMM, INIT:CONT.
B.182 TRIGger:SOURce? QUERY
TRIG:SOUR?
Syntax
:
Short Form: TRIG:SOUR?
Long Form: TRIGger:SOURce?
Returns: BUS, IMMEDIATE or EXTERNAL
Description:
Identifies whether internal, immediate or external trigger is activated.
TABLE B-6. ERROR MESSAGES
ERROR MESSAGE
ESR ERROR BIT SET
(SEE PAR. A.5)
EXPLANATION
0,“No error”
None
No error
1,”Interprocessor communications error”
Device Error bit 3
(1)
Interprocessor communications error
2,”Configuration error”
Device Error bit 3
(1)
Configuration error
10,”Program Error”
Device Error bit 3
(1)
Program error
(1)
The Device error bit may be set when the status monitoring functions of the power supply detect an overvoltage/under-
voltage condition.
SYST:VERS?
Unit returns 1997
SYST:SET?
Unit returns DC0,LF0,RL0,OUT0
SYST:PASS:NEW DEFAULT,OKAY
Unit changes password to be OKAY
SYST:SET LF1,RL1,DC1
Configures Device Clear, Line Feed and Reset
(see PAR. B.178).
SYST:PASS:CEN OKAY
Password enabled commands are accepted
MEM:UPDATE INTERFACE
Unit saves the LF1 state for next power on cycle.
Содержание BOP-ME 1KW
Страница 2: ......
Страница 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 42: ......
Страница 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 76: ......
Страница 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Страница 164: ......