OUTPUT CHARACTERISTICS (Continued)
Voltage stabilization in
voltage mode
source effect
0.05% of rating
min-max input voltage, 230V a-c reference
load effect
0.1% of rating
0-100% load current
time effect (drift)
0.02% of rating
0.5 through 8 hours
temperature effect
0.02%/deg C of rating
0 to 50 deg C
ripple and noise
(2% EOmax) p-p/(0.2% EOmax) rms Full scale, nominal resistive load; includes
switching noise
Current stabilization in
current mode
source effect
0.05% of rating
min-max input voltage, 230V a-c reference
load effect
0.2% of rating
0-100% load voltage
time effect (drift)
0.02% of rating
0.5 through 8 hours
temperature effect
0.02%/deg C of rating
0 to 50 deg C
ripple and noise
2% IOmax p-p / (0.2% IOmax) rms
Full scale, load is shunt only; includes switch-
ing noise
Output isolation voltage
d-c or p-p
300V (500V for BOP 10-100MG/ME)
Output to chassis ground
d-c leakage current
0.1mA @ 300V
(0.1mA @ 500V for
BOP 10-100MG/ME)
GND-NET to GND link not installed.
(4)
Error sensing
0.25V or 1% of voltage rating per wire
(whichever is less)
Above rated output
(5)
Transient recovery in
voltage mode
maximum excursion
5% of nominal output
nominal voltage, 50% load step
Recovery time
200
S
Return within 0.1% of set voltage
Series operation
Master/slave
Maximum of identical 3 units,
up to 300V max.
Parallel operation
Master/slave
Maximum of 5 identical units
Series-parallel Operation
2 series x 2 parallel
3 series x 2 parallel
Master/slave for both series and parallel
branches of identical units
Power-up timing
(parallel, series and series-parallel systems)
15 Sec max.
For system to be able to respond to analog or
digital control.
Output Protection
limiting
Analog Voltage and current limited in four quadrants, adjustable between 10% and 101%of
EO
NOM
or IO
NOM
. The analog limits are converted to digital limits at 100ms update
rate.
Digital Voltage and current limited in four quadrants, adjustable between ±Internal minimum
EO
MIN
or IO
MIN
(box) (see Figure 1-3) and ±1.01 EO
NOM
or IO
NOM
.
(4) With GND-NET to GND link installed: 0.55mA at 300V (0.91mA at 500V for BOP 10-100MG/ME).
(5) Remote error sensing applies to the main voltage channel. Feedback for the ±voltage limit channels is supplied locally from the
power terminals. Consult factory for a remote sensing solution applicable to the voltage limit channels.
TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
CONDITION
Содержание BOP-ME 1KW
Страница 2: ......
Страница 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 42: ......
Страница 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 76: ......
Страница 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Страница 164: ......