BOP HIPWR 091719
2-21
2.8.1
MULTIPLE UNIT CONNECTIONS
Before connecting the units in parallel or in series, configure each for master or slave (see PAR.
2.8.4), and save for power up. Then turn off the units and proceed with the parallel or series con-
nection. Figures 2-11 (local sensing) and 2-12 (remote sensing) show the connections for three
parallel-connected units; Figures 2-13 (local sensing) and 2-14 (remote sensing) show the con-
nections for three series-connected units. These figures allow other configurations, e.g., five
parallel-connected units or two series connected units, etc. to be easily deduced. Figure 2-19
shows the connections for a typical 3 X 2 (two parallel branches each consisting of three series-
connected units) configuration, as well as simplified diagrams showing required arrangements
for 2 X 2. Consult factory for configurations requiring more than two units in parallel or series.
CAUTION: For both parallel and series configurations, remove links between (COM S)
and (COM OUT) terminals of all slaves to prevent damage to the unit and
maintain system accuracy. Make sure to accurately follow Figures 2-11
through 2-14 for proper connection of the units.
The following connections are required.
•
Power cables
•
Sense connections (either local or remote)
•
All interconnection cables and terminations required for parallel, series, 2 X 2 or 3 X 2
configurations are supplied in the applicable Interconnection Kit (see Table 1-4 for part
number).
Содержание BOP-ME 1KW
Страница 2: ......
Страница 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 42: ......
Страница 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 76: ......
Страница 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Страница 164: ......