BOP HIPWR 091719
2-3
TABLE 2-2. IEEE 1118 CONNECTOR INPUT/OUTPUT PIN ASSIGNMENTS
CONNECTOR
PIN
SIGNAL NAME
FUNCTION
IEEE 1118 (BITBUS)
PORT
(connector A1J4)
1, 3 (shorted)
CONTROL BUS “A”
IEEE 1118, referenced to pins 5, 8
(2-Wire Differential Interface)
5, 8 (shorted)
CONTROL BUS “B”
IEEE 1118, referenced to pins 1, 3
(2-Wire Differential Interface)
6
TERMINATOR
Connect to pin 5 or 8 to add an internal termination resistor
to first/last unit on the daisy chain.
TABLE 2-3. TRIGGER PORT PIN ASSIGNMENTS
CONNECTOR
PIN
SIGNAL NAME
FUNCTION
TRIGGER PORT
(connector A1J3)
1
LOGIC GND
Return for TRIGGER and OUTPUT ON-OFF signals.
2
OUTPUT ON-OFF
Operation of pin 2 is controlled from either the front panel (PAR.
3.3.6: LowPulse, HighIsOn, LowIsOn, HighIsOff,
LowIsOff, OFF) or by OUTP:CONT command (PAR. B.23: LPLS,
HON, LON, LOFF, HOFF, OFF).
Factory default is LowPulse upon power-up: Logic 0 ((0 volts or
short circuit) for at least 100
S disables the output and puts the
unit in standby, however Logic 1 (TTL or 5V CMOS level) does
NOT enable the output. STANDBY key or a remote OUTP ON
command must be used to enable the output. Response to this
signal is relatively slow (200mS max).
HON: Logic 1 or open (not connected) = output is on (enabled);
Logic 0 = output is off (disabled). HON is shown as
HighIsOn
when configuring from front panel (see PAR. 3.3.6)
LON: Logic 0 or short = output is on (enabled); Logic 1 or open
(not connected) = output is off (disabled). LON is shown as
LowI-
sOn
when configuring from front panel (see PAR. 3.3.6)
LOFF: Logic 0 or short = output is off (disabled); Logic 1 does not
enable the output; STANDBY key or remote OUTP ON command
must be used to enable the output. LOFF is shown as
LowIsOff
when configuring from front panel (see PAR. 3.3.6)
HOFF: Logic 1 or open (not connected) = output is off (enabled);
Logic 0 does not enable the output; STANDBY key or remote
OUTP ON command must be used to enable the output. HOFF is
shown as
HighIsOff
when configuring from front panel (see PAR.
OFF - Pin 2 is disabled and the unit does not respond to signals
applied to this pin. Either OFF or STANDBY is required if using
OUTP ON and OUTP OFF commands to control the output.
3
NOT USED
4
EXT. TRIGGER INPUT
Logic 0 causes a trigger event. Logic 1 (TTL or 5V CMOS level)
rearms the trigger feature.
Содержание BOP-ME 1KW
Страница 2: ......
Страница 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 42: ......
Страница 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 76: ......
Страница 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Страница 164: ......