background image

25% load

50% load

75% load

100% load

85.5%

91.7%

92.8%

92.9%

89.0%

92.4%

92.8%

92.6%

25% load

50% load

75% load

100% load

95.5%

97.6%

98.3%

98.5%

96.6%

98.1%

98.5%

98.7%

Heat rejection in Double Conversion operating mode

@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected

25% load

50% load

75% load

100% load

29295

31270

40207

52807

BTU/hr

8.6

9.2

11.8

15.5

kW

28466

37888

53609

73623

BTU/hr

8.3

11.1

15.7

21.6

kW

Heat rejection in eBoost Operating mode

@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected

25% load

50% load

75% load

100% load

8140

8495

8962

10522

BTU/hr

2.4

2.5

2.6

3.1

kW

8106

8922

10522

12134

BTU/hr

2.4

2.6

3.1

3.6

kW

Max Cooling Air (77°F - 86°F / 25°C - 30°C) (225/300kVA)

Double Conversion Mode

eBoost Mode

UPS

Battery

UPS

Battery
(VRLA)  

Relative humidity

ft (M)

4921ft

(1500Mts)

6562ft

(2000Mts)

8202ft

(2500Mts)

9843ft

(2500Mts)

ft

(M)

-5%

-9%

-14%

-18%

Derating

System Efficiency in Double Conversion operating mode

@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected

(Note: Higher temperatures shorten battery life)

(Note: Higher temperatures reduce battery storage time)

300kVA with 5th filter

3281 / 1000 (no derating)

60 dB(A)

32°F - 104°F (0°C - 40°C)
68°F - 77°F (20°C - 25°C)

Operating temperature range

Audible noise level (at 5 ft./1.52Mts)

67 dB(A)

300kVA with 5th filter

300kVA with 5th filter

225kVA with 5th filter

2661 / 3709 CFM

Digital Energy
SG Series Uninterruptable Power Supply
225-300kVA UL listed with eBoost

TM

Storage time is 6 months at 77°F (25°C). 

Topology

System Efficiency in eBoost Operating mode

@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected

225kVA with 5th filter

General Data

Nominal output power at pf = 0.9 lag.

g

Technical Data Sheet - 225-300kVA UL Listed

300kVA with 5th filter

225kVA with 5th filter

True On-line double conversion

300kVA (270kW) / 225kVA (202.5kW)

0-95%, non-condensing

Maximum Altitude

225kVA with 5th filter

32°F - 104°F (0°C - 40°C)

5°F - 122°F (-15°C to +50°C)

Storage temperature range

Energy

Digital Energy

g

 

imagination at work

GEA-D2041  (225 300kVA TDS),  Page: 1