Technical Data Sheet - 225-300kVA UL Listed

Energy

Digital Energy

Type:

Safety:

Cooling:

Color:

Rigging:

Mounting:

Installation and maintenance access:

Conduit Entry:

Standards
Electrostatic discharge immunity

Standard:

Optional:

Fault current rating

Configuration

Voltage:

Frequency:

Harmonic Current Distortion:

Power Factor (Typical):

Inrush current:
Power walk-in:

Output Voltage Tolerance:

DC ripple voltage:

DC ripple current:

Nominal input (100% load)

Current[A]:

(0.9 PF load, fully chrg'd bat.)

kVA

kW

Maximum input (100% load)

Current[A]:

(0.9 PF load, max. chrg current)

kVA

kW

Max. charge current

A:

Battery compatibility
Number of cells
Float voltage at 68°F (20°C)
Minimum discharge voltage
Recharge time for 30 minute battery
Battery ground fault detection
Automatic and manual battery test

UPS Rating

(kVA)

@100% load, 0.9 PF lag                                                                        

kWB:

Maximum Discharge Current                                                          

A:

718

Enclosure

Limited by soft-start circuit

Suitable for handling by forklift

Battery

Lead-acid or NiCd, VRLA or flooded

4kV contact / 8kV air discharge

Top and Bottom standard

225

300

60Hz, +/-10% (54-66Hz)

Installation

Rectifier

Indoor (IP20) and NEMA PE 1

Internal dead front construction

Forced Air (Redundant Fans)

(-20% to +15% without battery discharge)

Redundant Parallel Architecture (RPA) - up to 6 units may be paralleled 

in any combination for redundancy or capacity

NOTE 1: 

The Bypass input must be fed from a grounded-WYE electrical system. refer factory for 3-wire operation on bypass input. The load 

cannot use neutral unless the bypass input feeder includes neutral.

480VAC, 3-phase, 3 wire + ground (NOTE 1)

Configuration

Six Pulse Thyristor, Three phase bridge

UL 1778, IEC 62040, ISO9001, FCC Class A Optional

Black (RAL 9005)

Stand-alone

UPS is designed for installation in an electrical system up to 65kA

Input

Floor mounting holes provided

Front access required for normal maintenance

213.0

Standard
Standard

540VDC

<7.5% (225kVA) / <7% (300kVA)

284.0

10 times the discharge time

538

450.0

220.0

338.0
240.0

396VDC (adjustable)

319.0

30 seconds (Adjustable)

0.93 lagging

294.0
490.0
351.0
323.0

60

275.0
252.0

300

225

60

380.0

UPS Rating Vs. current limits

240 (lead-acid)

 +/- 1%
 +/- 1%

Max. 5% of battery capacity expressed in amps

g

 

imagination at work

GEA-D2041  (225 300kVA TDS),  Page: 2