Technical Data Sheet - 225-300kVA UL Listed

Energy

Digital Energy

Nominal output voltage
Inverter bridge
Output Isolation transformer
Output waveform

Static:

Load step 0% - 100% - 0%:
Load step 0% -   50% - 0%:

100% unbalanced load (Ph-N):

100% linear load:

100% non-linear load (per IEC 62040):

Crest factor capability
Output neutral rating

100% balanced load:

100% unbalanced load:

Free running:

Synchronized with utility:

Overload capability (on inverter)

Short circuit capability (on inverter)

UPS Rating

(kVA)

Maximum Output Current @ 0.9pf

A

Input configuration

Transfer limits

Short circuit capability (on bypass)

Input wiring configuration
Output waveform
Transfer time (static bypass to Inverter)

Steady-state RMS tolerance

Magnitude

Duration

Steady-state frequency tolerance
Instantaneous phase shift

1000% for 1/2 cycle (non-repetitive)

360.0

270.0

300

eBoost™ Operating Mode

+/-3 Hz

125% at 0.9 PF for 10 minutes.

< 3:1

200%

 +/- 1%

True sine wave

Output frequency

Output voltage distortion

60Hz, +/- 0.01%

 +/- 3%, recovering to /- 1% in 1 cycle

Inverter

Standard

IGBT technology and Space Vector Modulation

480VAC, 3-phase, 4 wire + ground (NOTE 1)

 +/-2%, recovering to /- 1% in 1 cycle

Full load rated static switch

Back feed prot Semiconductor fuse for clearing fault currents

 +/- 4% (adjustable from 57.6Hz to 62.4Hz)

Phase displacement

 +/- 3%

2% THD maximum

120°+/- 1%
120°+/- 2%

3% THD maximum

225

Common with rectifier (default) or dual input (optional)

Static Bypass

Internal maintenance bypass (optional)

 +/- 10% of nominal output voltage (adjustable)

Instantaneous voltage distortion

(with respective to Normal Sine wave)

Output voltage tolerance                                                     

700% of rated current for first 1.2 ms followed by 

220% for 100 ms, electronically limited

150% at 0.9 PF for 30 seconds

Transfer limits

+/-75Vp

+/-20 Vrms (adjustable)

500µs (adjustable)

110% continuous

200% for 5 minutes

480VAC, 3-phase, 4 wire + ground (NOTE 1)

Primary components

Overload capability (on bypass)

0.15 radians (8.5 Deg)

Continuously monitored

<4ms (typical)

g

 

imagination at work

GEA-D2041  (225 300kVA TDS),  Page: 3