Engineering manual - UniSAB III 1.10.8
182/346
001930 en 2021.06
8: Multisab Master
Start#
Compr#
If selecting
Compr#
, the compressor with the lowest compressor number will always be the regulator in
a Multisab system independent of the starting sequence. If selecting
Start#
, the compressor with the
lowest starting number and which is in
Remote/Multisab
will be the regulator.
6.2
Sequencing
6.2.1
Multisab sequencing
Multisab is a distributed compressor control system which is very useful when more compressors are
working together (e.g. connection to the same suction line). With Multisab it is possible to start, stop and
capacity regulate compressors according to the varying cooling requirements.
Multisab is a standard function in UniSAB III. The system is described in detail in the UniSAB III se-
quence manual. In order for Multisab to work, all UniSAB III units which should participate in the distrib-
uted control must be physically connected via the Danbuss communication network. Fig. 45 in
subsection
8.5.3 Configuration of RS485 port/Danbuss
describes how to connect the units.
To get optimal use out of Multisab it is very important that certain key parameters are selected correctly
by the user as explained in subsection
Multisab regulation
. To explain the contents of the
Sequencing
picture, the following key parameters are described here:
Compr. no, Start no, System no, System regu-
lator, Multisab Master, Compr. Mode, Compr. Status, Multisab Status
and
Control Mode
.
6.2.2
Sequencing parameters
Always make sure that all UniSAB III units on a network have different compressor numbers, i. e. two
units are not allowed to have the same
Compr. no
. See subsection
.
System no
tells Multisab which compressors are going to work together.
Fig. 23 below shows two examples.
Fig. 23: Examples of compressor systems
In the left example two separate compressor plants are connected on a common Danbuss network. In
this system it is very important that:
UNISAB
UNISAB
UNISAB
UNISAB
UNISAB
UNISAB
UNISAB
UNISAB
Suction line, sub-plant 1
System no. = 1
System no. = 2
Suction line, sub-plant 2
Compr. 1
Compr. 2
Compr. 3
Compr. 4
Separated compressor plants
Common compressor plant
Common
Multisab
network
Multisab
network
System no.
= 1 or 2
Suction main line 1
System no. = 1
Suction main line 2
System no. = 2
System no.
= 1 or 2
System no
= 1 or 2
System no.
= 1 or 2
Compr. 1
Compr. 2
Compr. 3
Compr. 4
Содержание SABROE Unisab III Control
Страница 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Страница 2: ......
Страница 347: ......