Engineering manual - UniSAB III 1.10.8
238/346
001930 en 2021.06
No.
Value
Factory
Low
High
Unit
Adjust-
able
53 Fan delay
60
0
1200
Sec.
Yes
54 Oil pump low alarm
30
0
600
Sec.
Yes
55 Oil pump low shutdown
120
0
900
Sec.
Yes
56 Backspin delay
1
0
10
Sec.
Yes
57 Vi position alarm
30
0
300
Sec.
Yes
58 Discharge diff. delay
300
0
300
Sec.
Yes
59 Discharge diff. start
900
300
1500
Sec.
Yes
Table 52: Timer values - screw compressors