Engineering manual - UniSAB III 1.10.8
174/346
001930 en 2021.06
Reading
7
5910
Input (Amp AC)
0
1.0
Table 40: Current
Table 35 in subsection 4.1.1 shows the numbering of analogue inputs.
Analogue outputs
This picture shows which analogue output value (in percentage) UniSAB III is transmitting to the con-
nected equipment. The signals are 4-20 mA signals and can e.g. be used to regulate the speed of a fre-
quency converter or to open a motor valve. When using analogue regulation of the frequency converter,
the capacity and Vi slides can be regulated digitally at the same time.
As long as the above menu picture is shown in the display, test mode =
Yes
and a test value between 0
and 100% can be selected. UniSAB III will then transmit an mA signal corresponding to the test value.
Note:
Do not let the compressor motor run when using test mode as the motor revolutions will follow the
changes in the signal. However, test mode can be used to check whether the frequency converter re-
ceives the signal correctly by reading the analogue input signal in the menu system of the converter.
Digital inputs
This picture shows the actual state of the digital inputs both at compressor standstill and during opera-
tion.
0 = Input open
1 = Input closed
Table 33 and Table 34 in subsection 4.1.1 show the numbering of the digital inputs and outputs.