Compressor control and surveillance
3.5.7
User input
In the
Configuration/External Input
menu the following picture appears:
Place the cursor on
Function
. Press
and with
and
choose between:
•
Not used
•
Suction pressure setpoint
•
Process out setpoint
•
Discharge pressure setpoint
•
Hot water setpoint
•
Capacity setpoint
•
External input signal
This function is connected to an analogue input. See wiring diagrams.
Explanation
•
Not used
The input signal is not used and alarm/shutdown supervision for this input is disabled.
•
Suction pressure set point
The signal is used as a set point reference for the suction pressure regulator.
•
Process out temp. (Brine) set point
The signal is used as a set point reference for the process out temperature regulator.
•
Discharge pressure set point
The signal is used as a set point reference for the discharge pressure regulator.
•
Hot water set point
The signal is used as a set point reference for the hot water temperature regulator.
•
Capacity set point
The signal is used as a set point reference for the capacity regulator.
•
User 1 (External) input signal
The signal is used as input signal for the User 1 (External) regulator.
See also subsection
3.1.10 User input regulator (Ext. input)
for a more comprehensive explanation and
set up examples of
User input 1
.
3.5.8
Motor current measuring
UniSAB III can be supplied with a 0-1 Amp AC signal directly from a current transformer in the compres-
sor motor starter or supplied with a 4-20 mA signal from a current transmitter/VSD.