Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
79/346
Compressor control and surveillance
Settings regulating parameters, SABCube and SABflex
Start-up limiter
Regulator type
Para-
meter
Minimum
Maxi-
mum
Factory
setting
Unit
Start-up limiter
High internal suction
pressure
Nz
0.0
2.0
0.3 (SABCube)
0.0 (SABflex)
bar
Pb
0.0
100.0
1.0
bar
T.int.
0.0
100.0
60.0
sec.
Run time
0.2
6.0
0.4
sec.
Start-up limiter
Low oil pressure
Nz
0.0
2.0
0.3 (SABCube)
0.0 (SABflex)
bar
Pb
0.0
100.0
1.0
bar
T.int.
0.0
100.0
60.0
sec.
Table 21: Settings - regulating parameters, SABCube and SABflex
Start-up limiter
Settings - Regulating parameters, chiller level control
Regulator type
Para-
meter
Minimum
Maximum
Factory
setting
Unit
Level control
Sp 1
0
100
30
%
Nz
0
10
2
%
Pb
0
200
10
%
Ti
0
999
30
sec.
Td
0
999
0
sec.
Table 22: Settings - regulating parameters, chiller level control
Settings - Regulating parameters, SAB 330
Regulator type
Parameter
Factory
setting
SAB 330
Capacity control
Nz
Hydraulic
Mechanical
Pb
0
2
Min. pulse
200
200
Run time
1
2
Vi slide control, compressors
with automatic Vi regulation
Nz
See note 1
See note 1
Pb
4
10
Min. pulse
200
200
Run time
1
1
See note 1
See note 1
Table 23: Settings - Regulating parameters, SAB 330
Note 1
. Run time factory settings are as follows:
SAB 330 S
SAB 330 L
SAB 330 E
Others
Unit
Cap. run time
41
56
74
60
sec.
Vi run time
19
24
31
60
sec.
Table 24: Run time factory settings