Engineering manual - UniSAB III 1.10.8
80/346
001930 en 2021.06
Compressor control and surveillance
Note 2
. Run time factory settings for SAB 120
→
355 and SAB 273 S:
SAB 120
SAB 151
SAB 193
SAB 233
283
355
273 S
Unit
Cap. run
time
30
30
40
50
60
60
60
sec.
Vi run
time
NA
NA
20
25
30
30
30
sec.
Table 25: Run time factory settings
Settings - regulating parameters, reciprocating compressors
Regulator type
Para-
meter
Minimum
Maximum
Factory
setting
Unit
Suction pressure
Sp 1
-1
-90
9
24.8 (1*)
1
-19.1
bar
°
C/R717
Sp 2
-1
-90
9
24.8 (1*)
1
-19.1
bar
°
C/R717
Nz
0
100
4
°
C
Pb
0
100
10
°
C
Process out
temperature
(Brine)
Sp 1
-60
100
20
°
C
Sp 2
-60
100
20
°
C
Nz
0
100
4
°
C
Pb
0
100
10
°
C
Discharge side
Sp 1
-1
-90
24
58 (2*)
8
21.4
bar
°
C/R717
Sp 2
-1
-90
24
58 (2*)
8
21.4
bar
°
C/R717
Nz
0
100
4
°
C
Pb
0
100
10
°
C
Process out
temperature
(Hot water)
Sp 1
-60
100
20
°
C
Sp 2
-60
100
20
°
C
Nz
0
100
4
°
C
Pb
0
100
10
°
C
Ext. cool
Sp1
-999
999
0
-
Sp2
-999
999
0
-
Nz
0
999
0
-
Pb
0
999
0
-
Ext. heat
Sp1
-999
999
0
-
Sp2
-999
999
0
-
Nz
0
999
0
-
Pb
0
999
0
-
Motor current limiter
Sp1
0
2500
2500
Amp.
Sp2
0
2500
2500
Amp.
Notes
:
1* HPO/HPC +25 bar (+60°C/R717)
2* HPO/HPC +42 bar (+82°C/R717)
Table 26: Settings - regulating parameters, reciprocating compressors
Содержание SABROE Unisab III Control
Страница 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Страница 2: ......
Страница 347: ......