Engineering manual - UniSAB III 1.10.8
240/346
001930 en 2021.06
8. Oil flow
When prelubrication is initiated, a signal must be issued from the float switch before the timer expires;
otherwise an error message appears.
1) For SAB 202, SAB Mk 3 and VMY Mk 3.
2) For SAB 163 Mk 1.
3) For SV 10/20 and FV 10/20
4) For SAB 283, SAB 355, GSV, RWF and SAB 330 B. (B is short for Booster, which can be selected in
the
Config.
menu).
5) For SAB 330 HP. (HP means Booster = No).
6) For SAB 120
→
151, SAB 193
→
355, SAB 193 H
→
355 H, SAB 157 HR, SAB 273 S and SABflex prelu-
brication is not used.
9. Oil flow switch delay, start
When starting a compressor, a time delay ensures that the oil float has time to lift.
1) For SAB Mk 2 110/128/163 and SAB 80.
2) For compressors with prelubrication delay = 0 sec.
3) For SV 10/20 and FV 10/20
4) SAB 120
→
151 SAB 193
→
355, SAB 193 H
→
355 H and SAB 273 S (Not used)
5) SABflex and SABCube
6) SAB 157 HR (Not used)
10. No oil/flow
During operation the oil float is allowed to be disconnected only for the time period stated.
1) For SAB 110, 128, 163, 202 and VMY compressors
2) For SV 10/20 and FV 10/20
3) For GSV/RWF
4) For SAB 80
5) SAB 120
→
151, SAB 193
→
355, SAB 193 H
→
355 H, SAB 157 HR and SAB 273 S
6) SABflex and SABCube
11. Lubrication time/flow
After start-up of compressors with prelubrication pump, the pump will run for the time stated after com-
pressor start.
1. For SAB 202, SAB Mk 3 and VMY Mk 3, SV 10/20 and FV 10/20
2. For SAB 163 Mk 1
12. Diff. pressure OK
For VMY Mk 3, SAB Mk 3, SAB 202, SAB 283 Mk 1, SAB 355 Mk 1, SV 10/20 and FV 10/20 the oil pump
will run for the stated time after the desired differential pressure has been reached. The timer is also
used for SAB 120
→
151, SAB 193
→
355, SAB 193 H
→
355 H, SAB 157 HR and SAB 273 S compressors if
fitted with oil pump.
13. Oil pressure low
During start the shutdown for low oil pressure is delayed for the stated time. No delay during normal
operation.
1) For SAB 202, SAB Mk 2, SAB Mk 3, VMY, SAB 80, SAB 283 Mk 1, SAB 355 Mk 1, SV 10/20 and FV
10/20.
2) For SAB 163 Mk 1
Содержание SABROE Unisab III Control
Страница 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Страница 2: ......
Страница 347: ......