Set-up/Configuration
No.
Function
Use
Choices
Communication
1
Compressor *
1/2
No. 1-14
2
Baud rate *
1/2
1200, 2400, 4800, 9600, 19200
3
Danbuss master enable
1/2
No, Yes
4
Profibus *
1/2
Yes, No
5
Profibus node no. *
1/2
1 to 254
6
Profibus baud rate
1/2
Auto adjust (9600-1.5 M)
7
GSD file no. *
1/2
08AA, 095D
8
Dig. input by com
1/2
Off, Modbus, Profbus
9
Evolution
1/2
No, Yes
Measuring
1
Pressure/temperature **
1/2
Bar/
°
C/R, Psi/
°
F, kPa/
°
C
2
Pressure range **
1/2
9/25/25/25, 25/59/25/25, 25/59/59/59
3
Low suction pressure
1/2
Yes, No
4
Capacity signal
2
Cap. pos, Freq.
5
SMC LL
1
No/Yes
6
Suction pressure gradient reset
1/2
0.0 to 20.0 *C [3.0 *C]
7
Yield rate up limitation
1/2
0.2 to 3.0 %/sec [2.0 %/sec]
8
Yield rate down limitation
1/2
0.2 to 3.0 %/sec [1.0 %/sec]
External (user 1) input
1
Function
1/2
Not used, Suction pressure setpoint, Process out
setpoint, Discharge pressure setpoint, Hot water
setpoint, Capacity setpoint, External input signal
2
4 mA
1/2
-999.9 to 999.9
3
20 mA
1/2
-999.9 to 999.9
Aux. output
1
Activate when
1/2
Not defined, Ready, At min. cap., At max. cap.,
Running, Ready ext., Ready/me only, Running at
max. cap.
2
Signal low
1/2
0 to 100
3
Signal high
1/2
0 to 100
Quick Setup
1
Rotatune *
1/2
No, Yes
2
Compressor type **
1/2
Screw or reciprocating compressor
3
Refrigerant. **
1/2
Not defined, R717, R22 etc.
4
Compressor *
1/2
1-14
5
Baud rate *
1/2
1200, 2400, 4800, 9600, 19200
6
GSD file no *
1/2
08AA, 095D
7
Profibus *
1/2
No, Yes
8
Profi Node no. *
1/2
1 to 254
9
Press/temp **
1/2
Bar/
°
C/R, Psi/
°
F, kPa/
°
C
Factory reset
1
Factory reset **
1/2
Yes, No
Table 44: Set-up/configuration
The configuration points are divided into sub-menus composed as follows: