Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
189/346
Set-up/Configuration
No.
Function
Use
Choices
Drive
1
Motor range Amp
1/2
0 to 2500 Amp
2
Motor range kW
1/2
0 to 2500 kW
3
Motor nom. kW
1/2
0 to 2500 kW or Amp
4
Display
1/2
Amp or kW
5
Motor input signal
1/2
0-1 A/4-20 mA
6
Rotatune *
1/2
No, Yes
7
Drive Com
1/2
AO, LS, DA
8
Motor rpm min.
1/2
500 to 1000 rpm (1) / 0 to 12,000 rpm (2)
9
Motor rpm max.
1/2
1100 to 1800 rpm (1) / 0 to 12,000 rpm (2)
10
Forced speed
2
0 to 12,000 rpm
11
Drive cap limit
2
90 to 100%
12
Motor fan
2
No, Yes
13
Rota recip.
1
Step, Speed
14
Motor rpm min. 2
1
500 to 1000 rpm
Compressor block
1
Compressor type **
1/2
Screw or reciprocating compressor
2
Swept volume
1/2
0 to 12000 m
3
/h
3
Volume ratio
2
Manual, Auto
4
Fixed Vi ratio
2
1.4, 1.7, 2.2, 2.9, 3.4, 4.0
5
Vi comp. plug valve
2
No, Yes
6
Vi low range
2
No, Yes
7
Vi trigger level
2
NA
8
Vi mode (%)
2
70 to 97%
9
Mechanical zero
2
No, Yes
10
Manual zero
2
0 to 40%
11
Capacity zero
2
0 to 90% [60%]
12
Booster
2
No, Yes
13
Economiser
2
No, Yes
14
Eco low capacity
2
0 to 100%
15
Neutral zone
2
5 to 20%
16
Eco high suction pressure
2
-100 to 100
°
C/R
17
Unloading
1
Normal, Total, Additional steps, VSD Normal, VSD
Total
18
Unload assist
2
Yes, No
19
Capacity decrease assist rate
2
1 to 5%
20
Volume dead band
2
3 to 70%
21
Oil filter Diff.
1
No, Yes
22
Suction press. grad.
1/2
No, Yes