Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
211/346
16: Oil return evap.
No
Yes
Select
Yes
to use the
oil return from evaporator
function. See subsection
3.6.4 Oil return from evapora-
.
17: By-pass start
No
Yes
Select
Yes
to use the
by-pass start
function. See subsection
3.6.5 By-pass function (ChillPAC)
. When
choosing
by-pass start
it will not be possible to configure
21: Level control to LP or HP
.
18: Flow evap.
No
Yes
Select
Yes
to use the
flow evaporator
function. See subsection
3.6.6 Flow evaporator (ChillPAC/PAC)
19: Flow cond.
No
Yes
Select
Yes
to use the
flow condenser
function. See subsection
3.6.7 Flow condenser (ChillPAC/PAC -
20: Liquid level limiter (reciprocating compressors)
No
Yes
Select
Yes
to enable the
Liquid level limiter
function. See subsection
.
This function will reduce compressor capacity with approximately 3%/sec up to 33%, as long as the
liquid level is high. When the level is back to normal, and after a time delay, the compressor is allowed to
increase capacity.
Note:
This function is not available for SMC/TSMC/HPC reciprocating compressors produced before
2010 and equipped with an oil filter differential pressure switch. To use this function, the parameter
Set
up/Configuration/Compressor block/Oil Filter Diff.
must be set to
Yes
.
21: Level Control
Off
LP
HP
DX
Select LP or HP to use the LP or HP level control function. See subsection
and sub-
section
3.1.9 Set points for regulators
Select DX in order to regulate an expansion valve controlling the liquid filling in the evaporator according
to the suction superheat set point.
When choosing LP, HP or DX it is not possible to configure any kind of oil cooling for screw or reciprocat-
ing compressor. See
6.4.5 Oil system, 3: Oil cooling
.